A petrol leak was discovered on a 3” diameter pressure testing pipe of a flowmeter on a hollow tubular support. The operator had visually noted corrosion on the support already 3 years earlier. Replacement of the support was planned to take place during the regulatory shut-down period but was not performed. The ignition source was not precisely identified. Before the fire started, an alarm corresponding to the 20% lower explosive limit had been triggered 6 times, without the operators noticing. As some of the units had still been shut down, the alarms dedicated to the unit in operation were filtered. This filtering arrangement masked the display of the fire and gas alarms and only displayed those pertaining to the unit’s processes that had been restarted. The flashing light visible in the control room was considered a “process” alarm, knowing that such signals are not explicitly dedicated to fire and gas alarms.