IMPROPER OPERATION READINESS REVIEW DUE TO HUMAN FACTORS CAUSED AN INCIDENT

 On February 23, 2023, at 8:15 p.m., an accidental release of approximately 164 pounds of hydrocarbons (pentane and heavier hydrocarbons) occurred at a Refinery in Texas. The hydrocarbons were released from an open bleed valve on a crude unit heat exchanger during startup. The hot hydrocarbons ignited (autoignition), causing a fire that damaged nearby equipment. The company estimated the property damage from the incident to be $2.3 million.

On February 12, 2023, the crude unit heat exchangers were shut down for cleaning. Ten days later, on February 22, refinery operators prepared to put the heat exchangers back into service after the cleaning. During the day shift on February 23, they purged air from the heat exchangers to prepare it for startup.

Night shift operators then continued readying the heat exchangers for startup. They obtained the energy isolation drawing, which was used to document which valves had been locked in the open or closed position to allow for safe cleaning of the heat exchangers.
The operators walked down the equipment, removed the locks indicated on the energy isolation drawing, and ensured the valves were lined up in the correct position for startup. The operators believed they had addressed all the valves documented on the energy isolation drawing. Unknown to the operators, however, a bleed valve on top of the heat exchangers remained locked open when the lock should have been removed, and the valve should have been closed. The company's investigation report noted that the open bleed valve was not easy to locate visually, and the operators’ ability to see it may have been further impaired when it was dark outside.
As the startup sequence progressed, hot hydrocarbons sent to the heat exchangers flowed through the open bleed valve into ambient air and ignited. The material was released at 562 degrees Fahrenheit (°F) and had an autoignition temperature of 482 °F.
The company stated that the energy isolation drawing was destroyed in the fire; so it is unknown if the locked open bleed valve was shown on the drawing.
Probable Cause
Based on the company's investigation, the CSB determined that the probable cause of the incident was the release and ignition of flammable hydrocarbons when a bleed valve was inadvertently left open during an equipment startup. Contributing to the incident was a lack of a system, such as leak testing, to ensure all valves were in the correct position before the equipment was started up.

Source: CSB.gov

 

 

January 9, 2026

A LOOSE BEARING LOCKNUT CAUSES AN INCIDENT

On February 11, 2023, shortly before 1:00 p.m., a pump failure released hydrocarbons (primarily crude oil) and nitrogen oxide at a crude oil production facility in Texas. The crude oil released from the failed pump ignited, causing a fire that damaged nearby equipment and led to additional material releases The company estimated the property damage from the incident to be about $1.5 million.

The company's investigation found excessive wear and tear on the pump, which led to its failure. The company also found that the pump’s bearing lock nut, which holds the bearings in place, was loose. It concluded that this loose lock nut allowed the pump shaft to move and contact pump components, which caused pump damage that resulted in crude oil being released from the pump into the atmosphere. The company also concluded that heat from metal-to-metal contact in the pump seal area may have provided the ignition source.
During the incident, over 1,500 barrels of hydrocarbons (primarily crude oil) and over 1,200 pounds of nitrogen oxide were released.

Probable Cause
Based on the company's investigation, the CSB determined that the probable cause of the accidental crude oil release and fire was the failure of a crude oil pump. The released crude oil was likely ignited from heat from metal-to-metal contact in the worn pump.

January 5, 2026

INCIDENT DUE TO LACK OF PROPER CONTROL OF HAZARDOUS ENERGY

On January 19, 2023, less than five pounds of hot water and pulp were accidentally released, seriously injuring one employee at a paper mill in Georgia, a facility that produces paper products.
The employee had been tasked with inspecting and cleaning a pulp screen. The pulp screen equipment’s drain system had plugged (an abnormal condition), causing water and pulp to remain inside the equipment. With the plugged drain, the process conditions allowed the typically warm water to become hot.
When the employee started unbolting the equipment flange to access the screen, hot water and pulp sprayed out of the flange, contacting the employee. The employee received thermal burns requiring hospitalization. Miscommunication and ineffective training allowed the worker to open this equipment before it was effectively isolated and de-energized.
After the incident, the company added safety interlocks to shut down this equipment automatically during certain abnormal conditions.
Probable Cause
Based on the company's investigation, the CSB determined that the probable cause of the incident was opening equipment that contained pressurized hot water and pulp. Contributing to the incident was ineffective communication and training on the site’s procedure to control hazardous energy.

Source: CSB

December 31, 2025

HAPPY NEW YEAR!

 TO ALL MY BLOG FOLLOWERS, 

 


December 30, 2025

CHANGES CAUSE AN INCIDENT

 On August 29, 2024, at 6:45 p.m., flammable vapors were accidentally released from a reactor at a refinery in Houston, Texas, resulting in a fire at the facility. The incident resulted in $16.8 million in property damage.
At the time of the incident, employees noticed flames coming from the head of a reactor in the fluidized catalytic cracking unit (“FCCU”). The flammable vapor released from the reactor likely caught fire from autoignition because the reactor operated at 960 degrees Fahrenheit (℉), which is above the autoignition temperature for most of the hydrocarbons released. Unit operators put out the flames with a fire extinguisher. The company reported that over 400 pounds of flammable vapors were released during this incident.

The company’s investigation determined that the flammable chemicals were released through an 8-inch crack in the wall at the top (head) of the reactor. Additionally, the company found other cracks in the reactor that were up to 67 percent of the wall thickness. The cracks were created by a damage mechanism known as corrosion fatigue. Corrosion fatigue is caused by cyclically applied stress under corrosive conditions. Internal cracks formed at the top of the reactor, an area that was consistently exposed to sulfur-containing chemicals commonly found in petroleum refining. This sulfidation corrosion was coupled with temperature swings over 200℉, which applied stress to the vessel through expansion and contractions of the metal with the temperature changes. The company found that there had been more than 50 temperature cycles since 2011. Additionally, platform supports were added to the reactor head in 2001, contributing to the cracking by increasing the stress exerted on the vessel. Stress-assisted preferential sulfur penetration is the specific type of corrosion fatigue responsible for the 8-inch crack.

The investigation also revealed that the company was not inspecting the reactor’s walls for cracking because the site’s mechanical integrity program did not identify corrosion fatigue as a potential damage mechanism. The company attributed this gap to following industry standards that did not identify corrosion fatigue as a common FCCU reactor damage mechanism.

Probable Cause
Based on the company’s investigation, the CSB determined that the probable cause of the accidental release was an 8-inch corrosion fatigue crack through the wall at the top of the reactor. Adding platform supports to the top of the reactor contributed to the incident by increasing the stress exerted on the vessel during the temperature changes. The company’s mechanical integrity program contributed to the incident by not identifying corrosion fatigue as a potential damage mechanism for its FCCU reactor.

Source: CSB.gov