Pages

May 9, 2025

INCOMPATIBLE REACTION DURING PREPARING ACID CLEANING SOLUTION CAUSES H2S RELEASE

On March 29, 2023, at approximately 5:05 p.m., toxic hydrogen sulfide gas was accidentally released at a paper mill in Kentucky. Exposure to the hydrogen sulfide gas seriously injured one operator and injured two other operators.
At the time of the incident, three operators were tasked with circulating an acid-cleaning solution through process equipment to remove the buildup of solids impairing its performance. This task required an operator to stand directly over a tank and pour solid sulfamic acid powder into its opening.
When these operators added the sulfamic acid powder, the tank should have contained water, but a valve had been left open. This allowed a “weak wash” process stream to enter the tank before the operators added the solid sulfamic acid. The weak wash contained sodium sulfide, which reacted with the sulfamic acid, generating the toxic hydrogen sulfide gas.
Operator 1, who was standing directly over the tank opening, lost consciousness from exposure to the hydrogen sulfide gas that evolved from the tank. Operator 3 was able to call for help over the plant radio system but lost consciousness soon after. Operator 2 was seriously injured after losing consciousness (while trying to help Operator 1), falling to the floor, rolling through a guardrail system, and falling about 11 feet to a lower area of the structure.

Two other Domtar employees heard the distress call and entered the room to help the operators. All three operators regained consciousness. Operator 1 and Operator 3 were able to walk outside without assistance. Emergency responders transported Operator 2 to a hospital for treatment.The company reported that about 25 pounds of hydrogen sulfide were released.
 

Probable Cause
Based on the company's investigation, the CSB determined that the probable cause of the hydrogen sulfide release was the reaction between the added sulfamic acid and the sodium sulfide in the tank. The company's procedures did not indicate that the weak wash valve should be closed during normal operation, which contributed to the incident. Had the weak wash valve remained closed (or more robustly isolated), sodium sulfide could have been kept out of the tank, preventing the reaction that generated the toxic hydrogen sulfide.

Source:CSB.gov

May 8, 2025

Chiba, Japan,2011 (earthquake)

Chiba, Japan,2011 (earthquake) On 11 March 2011, the Magnitude 9 Great East Japan earthquake triggered multiple fires and explosions at the Liquefied Petroleum Gas (LPG) storage tank farm of a refinery in Tokyo Bay. At least 5 explosions occurred, the biggest of which created a fireball of about 600 m in diameter. Missiles from the exploding LPG tanks damaged asphalt tanks located next to the storage area, leading to asphalt leakage into the ocean. 

The accident also caused other effects when debris impact and LPG dispersion triggered fires in two neighbouring petrochemical installations. The fires burned for 10 days. At the refinery, six people were injured, while three injuries were reported in the facility adjacent to the LPG tank farm. Overall, 1,142 residents in the vicinity of the industrial park had to be evacuated. 

Onsite, all 17 LPG tanks were destroyed and the refinery returned to full operation only 2 years after the accident. 

Sources: Krausmann, E. and A.M. Cruz (2013), Impact of the 11 March 2011, Great East Japan earthquake and tsunami on the chemical industry, Natural Hazards, vol. 67, p.811 Cosmo Oil (2011), Overview of the fires and explosion at Chiba refinery, the cause of the accident and the action plan to prevent recurrence, Press Release August 2, 2011, http://www.cosmo-oil.co.jp/eng/press/110802/index.html.

May 3, 2025

CSB PROCESS SAFETY TRAINING APPLICATION - FREE

The CSB has developed a new interactive training application focused on OSHA's Process Safety Management, or PSM, regulation. The training covers the 14 elements of PSM using the 2005 explosion at BP’s Texas City refinery as a model. You can download the program from this link. It is 1GB size.

You can also give feedback to them on further improving it. Kudos to the CSB!

 https://www.csb.gov/news/csb-process-safety-training-application-/

April 30, 2025

Natech incident - chlorine tank lifted due to flooding

4 tanks with 80 m3 storage capacity for liquefied chlorine in a store housing 5 tanks. The tanks contained different amounts of chlorine with some containing only gaseous chlorine as a residue after discharging, and some being filled up to 20% of their capacity. Each chlorine tank was located in a concrete basin designed to retain the entire tank contents.

This tank with a capacity of 80 m3 was involved in the chlorine release on 23 August 2002.

Description

After being flooded with water exceeding the 'hundred year water level' by 1.3 m, the empty and less filled tanks were lifted by the buoyancy forces according to Archimede's law and displaced from their normal positions. The upwards movement of the tanks deformed and lifted the walkways situated above the tanks.

The safety fittings of the full tank got caught in the walkway and were completely torn off as the walkway kept moving upwards. As a consequence of the valves being torn off from the full tank, a massive leakage of chlorine occurred.

 The plant had implemented 100-year anti-flooding measures. However, the flood exceeded the 100-year flood by 1.3 m, and the severity of the flood was not forecast by authorities and was hence not expected by the plant.

Lessons Learned

Lessons Learned on Equipment

After the accident, a guide-rail structure for vertical guiding of the tanks was installed. This will avoid unwanted horizontal motion of the tanks in case of displacement. This measure was accompanied by a segmentation of the walkways which will move together with the tanks in case of floating.

Lessons Learned on Organisational Aspects

Chlorine storage was reduced to 50% of the capacity before the accident and therefore to one storehouse only, thereby significantly reducing the accident risk.

Also, prior to each scheduled shutdown of the sodium hypochlorite plant, chlorine is removed from the manifolds and pipelines, and before each scheduled power outage or disruption of cooling water supplies, the pipeline connecting the tanks in the storehouse must be disassembled.


April 26, 2025

Partial leakage of hydrochloric acid due to earthquake

 About 11:35 on December 17th, 1987, a strong earthquake occurred during usual operation of a vinyl chloride monomer plant. The substation was stopped by a malfunction of an over-current relay due to the earthquake during emergency shutdown operation. Although the emergency power generator started, fluctuations of cooling water caused by the earthquake were incorrectly interpreted as a fall of a liquid level. The emergency power generator was stopped immediately by an interlock that mistook an abnormality with cooling water. Following the total power failure, the alkali circulation pump of the absorber stopped, and the gas was discharged.

Read the incident in this link