Pages

Showing posts with label Process design. Show all posts
Showing posts with label Process design. Show all posts

November 12, 2026

FIRE IN HYDROGEN LINE DUE TO SOIL SETTLEMENT

Fire broke out along a “transition corridor” combining several underground pipelines transporting hazardous substances, including hydrogen, kerosene and ethylene oxide. The fire was brought under control within a few minutes thanks to the limited size of the leak. Though no noteworthy consequences were observed, the incident was still taken seriously, given the presence of other pipes merged into the same corridor, some of which were transporting toxic gases.

According to the appropriate inspectorate, a hydrogen (H2) leak on an underground pipeline had been ignited by welding work performed nearby. Differential ground settlement with local deformation of the pipeline at the level of a cathodic protection system had caused the H2 leak. The type of ground (i.e. sandy soil) facilitated this settlement due to the presence of heavy equipment on the ground surface (e.g. drainage pump, construction vehicles) used for earthworks conducted to lay a new kerosene pipe.

Although the transport of hazardous substances via this transition corridor was being managed according to a procedure considered secure, a number of deficiencies were nonetheless identified; design calculations were thus required with respect to the acceptable load limits above such pipe clusters. In addition, a more active pipe monitoring programme was recommended.

Source:Aria database

September 11, 2026

PRECAUTIONS FOR TANKS WITH INBUILT HEATING COILS

 PRECAUTIONS FOR TANKS WITH INBUILT HEATING COILS:

Design of facilities: 

Three interacting elements need to be taken into account when designing installations, particularly in terms of their compatibility with the operating conditions: - the nature of the products stored: flammable or non-flammable, likely to generate decomposition products that are themselves flammable or even explosive, requiring or not requiring temperature control; - the materials used for the storage tanks: flammable or non-flammable, and must be resistant to the products stored; - the heating elements: essential or non-essential, electric or using a thermal fluid (steam, hot water, heat transfer fluid, etc.), sized for a specific heating power. 

Reliable control equipment: - products are present in the tanks to prevent heating if tanks are empty (level and weighing sensors, etc.) - temperature of the thermal fluids used, the products contained in the tank, the atmosphere in the tank, etc. (appropriately positioned probes and sensors); - heating is controlled by the presence of product and by temperature control; - no contact between the heating elements and the tank’s walls; - monitoring of all of the installation’s operating and safety parameters. 

Regulated operating conditions: - preventive maintenance of facilities and equipment to prevent failures; - operating and intervention instructions (concerning the start-up of facilities in manual or automatic mode, shut-down of heating systems before intervention requiring tank emptying, after all interventions, etc.) - training of personnel in procedures and operating instructions; - monitoring and supervision of the installations during operations (the night prior, at night, early in the morning); - verification that all instrumentation and control channels are operating correctly, that the servocontrol and command logic is functioning correctly, and verification of automatic operation programmers.

Source:Aria database

July 22, 2026

DO YOU CONSIDER ACCIDENTAL REVERSAL OF PNEUMATIC HOSE CONNECTIONS TO CONTROL SYSTEMS DURING HAZOP?

 A reactor exploded in a fine chemicals plant during the chlorination of an alcohol by thionyl chloride (SOCl2 ). The relatively non-exothermic reaction took place in a solvent medium (1,2 dichloroethane or DCE), under a slightly lower pressure and a temperature of 70°C maintained by means of steam injection. The reactor initially contained the SOCl2 in solution in the DCE, with the alcohol being added under close monitoring for 30 hours. 

At the time of the accident, the reactor was being fed for three hours by successive 200- litre loads of alcohol, with the first injection still incomplete. Monitoring performed by two technicians, one of whom was a trainee, included an hourly reading of both the temperature and pressure drop; no anomaly had been observed until that point. Upon hearing a noise accompanied by a break to the protective disc on the glass column connected to the reactor and noticing smoke around the disc joints, the technician turned the feeder control box selector switch to the “off” position. As he closed the alcohol feed valve and was making his way to the valve used to shut down steam injection, he spotted that leaking on the column was becoming more persistent. He immediately left the unit, requesting that a co-worker follow him out — at which point the explosion happened. A rupture disc calibrated at 0.3 bar and the glass fixtures on top of the device burst. The explosion or toxic gases emitted once the equipment had broken killed the trainee technician, who did not exit the premises quickly enough. 

The feeder was equipped with two valves. The upper one (loading side) was found in the closed position while the lower valve (reactor side) was open with a reversal of the pneumatic control hoses. These recordings supported the hypothesis of an accidental addition of water into the reaction medium via the feeder. The laboratory simulation of such an addition found that the SOCl2 hydrolysis with the formation of SO2 and HCl led to a sudden pressure rise. 

Source:Aria database

July 13, 2026

DO YOU HAVE BACK UP POWER TO SAFETY CRITICAL EQUIPMENT?

A transformer caught on fire at 7:45 pm on a production building’s basement floor at a pharmaceutical plant. The building’s electrical power was cut, causing shutdown of the reactors’ stirring and cooling mechanisms. An exothermic reaction that was taking place at the time became uncontrollable. The reactor’s rupture disc, calibrated at 4 bar, broke, and the explosion vent opened to protect the structural integrity of the reactor. A quantity of the reaction mix at 70°C, composed of several hazardous products, projected onto one employee and six fire-fighters in the vicinity and formed a 60-m² puddle on the floor. 

The plant operator activated the internal emergency plan and the facility was evacuated. The safety report conducted on-site had not identified any comparable scenario. No backup source had been allocated to ensure the continued operations of critical equipment. Activities assigned to the damaged building and associated solvent storage zone were suspended until the safety systems (fire detection control, both post and automatic extinction) were once again operational. A diagnostic assessment of all site electrical installations was performed, along with a study, on the backup power supply for critical equipment, dedicated to exothermic reactions, i.e.: cooling, stirring, temperature and pressure probes.

Source:Aria database

June 27, 2026

DOMINO EFFECTS DUE TO POWER NON AVAILABILITY NOT CONSIDERED DURING DESIGN

 In a Seveso chemical plant, a fire broke out at 12:59 pm in a substation supplying a hydrazine hydrate unit. An electrical fault on a cooling water pump caused a generalised short circuit on an electrical tower. The fire alarm was triggered at 1.00 pm. The fire spread to the other towers of the panel through the subfloor. The 400 V circuit breaker located upstream was blocked and did not function. The fault current passed through the 13,000 / 400 V transformer, there was overpressure and an oil leak followed by a primary side homopolar fault causing the 13 kV circuit breaker to trip. The absence of voltage caused the diesel generator set to stop but the switchover to the emergency system failed as the automatism was damaged by the fire. The smoke spread to the UPS room whose door remained opened. The UPS stopped when a high temperature (> 40 °C) was reached causing the loss of control and command on the process. The component switched over to safety mode. Due to the lack of power supply, the cooling system, agitation and the internal and external emergency plan siren were no longer functional. Since the ongoing reaction was exothermic, the reactor temperature and pressure increased. Several measures are taken such as designing an emergency cooling circuit, improving circuit breaker maintenance, sectoring UPS system, electric boards, generator sets, etc.

Source: Aria ACCIDENT ANALYSIS OF INDUSTRIAL AUTOMATION

June 17, 2026

INADEQUATE DESIGN PHILOSOPHY CAUSES AN INCIDENT

 At a facility producing carbonate and sodium bicarbonate, fire broke out at 7 am in an electrical cabinet containing transmission cables for the liquid part of the process. The blaze caused a complete loss of control for 2 hours and a shutdown of the process responsible for releasing 2 to 8 kg of gaseous ammonia (NH3) into the atmosphere, subsequent to the sudden stoppage of the gas scrubber. In addition, ammonium hydroxide was released into the plant’s accidental pollution retention basin following discharge of a brine tank; this water made its way into the nearby river given that retention basin controls and monitoring installations had become unresponsive. This discharge wound up causing the death of some 400_kg of fish. According to the facility operator, the heating of electrical cables, traced to worn insulation, had triggered the incident. The control system, composed of control stations, a connecting bus and an automated system programmed to monitor the process, had been designed with a critical point in the form of a «node» at the time of creating the site’s 1st control system (26 years prior), through which all automated system cables were routed. Whereas all electrical component supply lines had been backed up, the automated system cables ran through a single cable tray in the electrical cabinet.

Source: Aria ACCIDENT ANALYSIS OF INDUSTRIAL AUTOMATION

June 8, 2026

INCORRECT DESIGN OF SAFETY SYSTEM CAUSES AN INCIDENT

 Dimethyl sulphate (DMS) began leaking around 11 am at a chemical plant as the product was being loaded. The connection between the DMS container and the loading station consisted of disassembling the solid flanges, replacing the joint by a new part and reconnecting the container flanges to the unit’s pipe flanges. After initiating DMS loading in the control room, the field operator climbed down to inspect the container and, at that point, identified a leak on the flange connecting the container to the loading pipeline. He sounded the siren and the emergency light before pressing the emergency stop button. The next day, the plant operator concluded that the leak had been caused by poor clamping of the loading flange while the container was connected to the loading station. Moreover, the safety automated system was not activated because the pushbutton had not been held down long enough for its cycle length (1/10th of a second). All emergency stop pushbuttons were replaced by locking buttons throughout the site.

Source: Aria ACCIDENT ANALYSIS OF INDUSTRIAL AUTOMATION

May 31, 2026

LOOK ALIKES IN CONTROL ROOM CAUSES AN INCIDENT

Inside a petrochemical unit, a steam supply problem encountered at the site’s steam production plant caused activation of the cracked gas compressor. The steam cracker was immediately shut down and the gases routed to the flare, resulting in the flaring of 800 tonnes of a hydrocarbon mix between Saturday evening and Sunday end of the afternoon. The unit’s supply was being provided by 2 boilers, one serving as a backup to the other. During the incident, one of the boilers was taken off-line for maintenance, leaving just a single boiler running. The idle boiler had undergone numerous safety tests, one of which called for closing the intake valve. The test operator mistakenly closed the fuel intake valve on the operating boiler from the control panel, causing a significant and sudden drop in steam supply to the units. With the steam cracker shutting down immediately, the installations were degassed and the flare network used as a backup for hydrocarbon ignition. To mitigate this type of error, the site operator improved boiler differentiation appearing on the control room’s graphic interfaces.

Source: Aria ACCIDENT ANALYSIS OF INDUSTRIAL AUTOMATION

April 5, 2026

OPEN TOP TANKS CAN BE DANGEROUS!

On February 6, 2023, at 8:15 a.m., a release of a hot sodium hydroxide and water solution (“caustic slurry”) seriously injured two employees at an aluminum refinery in Louisiana

 On the morning of the incident, a team of operators was assigned to drain hot caustic slurry, at a temperature of approximately 195 degrees Fahrenheit (℉), from a tank with an open-top design. The operators closed the tank’s steam injection control valve before beginning the draining operation. During their initial attempt to drain the tank, the operators determined that the drain piping was blocked. They used compressed air to blow through the drain piping to clear the blockage. However, when they directed the air into the piping, caustic slurry erupted from the tank’s open top. The hot, corrosive liquid splashed onto two of the operators. After they washed off in a safety shower, the two operators were transported to a hospital, where they were admitted for treatment of their burn injuries. It was reported that approximately 80 gallons of caustic slurry had been released during the incident.
The company’s investigation revealed that bauxite ore had accumulated in the tank and blocked the drain piping. Additionally, although the steam control valve was closed, it was leaking, which resulted in the tank’s contents being heated beyond the target temperature of 180℉. The investigation also found that no isolation device was installed to prevent the air injected into the drain piping from entering the tank. Furthermore, it was noted that some operators were not wearing the required chemical suits while clearing the pipes. Among the injured operators, one wore the required chemical suit, goggles, and rubber gloves, while the other wore goggles and rubber gloves but not the chemical suit.

Probable Cause
Based on the comapny's investigation, the CSB determined that the probable cause of the incident was flowing compressed air into the bottom of an open-top caustic slurry tank. The air created a geyser-like eruption of hot (195℉) caustic slurry that sprayed onto two operators, resulting in serious burn injuries. The lack of an isolation device between the tank and the air injection location, as well as the lack of an effective procedure to clear the drain piping, contributed to the incident

February 9, 2026

EXPLOSION IN FLARE LINE

A series of severe electrical storms caused refinery wide unit shutdowns, including the fluidised catalytic cracking unit (FCCU). The crude distillation unit was shut down as a result of a fire, which had been started by a lightning strike. A process upset in the FCCU’s gas recovery section ultimately led to a high liquid level in the flare drum and several shutdowns of the wet gas compressor, together with other process anomalies. As a result of the wet gas compressor shutdown, there was a large vapor load on the FCC flare system, which led to a high liquid level in the flare drum. When the hydrocarbon liquid overflowed into the outlet line of this drum, the line ruptured due to mechanical shock and approximately 20 tonnes of flammable hydrocarbons escaped. This mixture found a source of ignition 110 m from the flare drum and subsequently exploded. This caused a major hydrocarbon fire at the flare drum outlet itself and a number of secondary fires.
Key learning points
The explosion was caused by flammable hydrocarbon liquid being continuously pumped into a process vessel that, due to a valve malfunction, had its outlet closed. The only means of escape for this hydrocarbon once the vessel was full was through the pressure relief system and then to the flare line. The flare system was not designed to cope with this excursion from normal operation and due to liquid breakthrough at the FCCU flare knock out drum, a failure occurred in the outlet pipe. The investigation revealed, that internal acidic corrosion also contributed to the pipeline rupture. Apparently, the company did not inspect the weakest points of the pipeline which were exposed to corrosion

Source:IChemE 


August 28, 2025

INCIDENT DUE TO LONE WORKING WITHOUT ENGINEERING SAFEGUARDS

During the morning of February 24, 2023, an unknown amount of hydrocarbons and hydrogen sulfide were accidentally released, fatally injuring an employee inside an enclosed building at an oil and gas facility in Dakota. The hydrocarbons and hydrogen sulfide displaced the oxygen in the building, and the employee asphyxiated in the oxygen-deficient atmosphere.

The employee was considered a “lone worker” who operated multiple oil and gas facilities in the local area. Some of the oil and gas equipment was housed inside enclosed, insulated buildings, allowing operators to work in a climate-controlled environment. At the time of the event, it was negative 26 °F outside, and the interior of the building where the incident occurred (approximately 8 feet tall and 90 square feet) was about 65 °F.
A pump inside the building was not operating as designed, causing an adjacent vessel to begin overfilling. To prevent the vessel overfill from causing the facility to shut down, the employee began manually draining the vessel and another nearby vessel, both of which were housed inside the building. To drain the vessel, the employee connected a temporary hose to it and drained its liquid, mostly water and hydrocarbons, into a bucket inside the building. The employee then left the building temporarily to conduct operations at other locations in the facility. During this time, the drained hydrocarbons vaporized inside the enclosed building and displaced oxygen. About twenty minutes later, the employee returned to the insulated building and may have accidentally knocked over the bucket of drained liquid. Additional hydrocarbons and hydrogen sulfide likely vaporized, further displacing the oxygen inside the building. The employee breathed in the oxygen-depleted atmosphere and asphyxiated.
The building where the draining occurred did not have detectors installed to monitor for hazardous gases, and it was not ventilated. The employee had a personal gas detection monitor, but it was turned off and in his truck. No company procedure was in place that provided instructions for safely draining liquids from vessels inside buildings.
After the incident, the company evaluated adding additional engineering controls (for example, hazardous gas detection and alarms, forced ventilation) to its enclosed buildings, developed a written procedure requiring that process fluids be drained outside of buildings, and enhanced training and supervisor verification requirements regarding the use of personal gas monitors.
Probable Cause
Based on the company's investigation, the OSHA inspection, and the local Sheriff’s Office investigation, the CSB determined that the probable cause of the incident was the displacement of oxygen inside an enclosed building after an operator drained process liquid into a bucket and the hydrocarbon and hydrogen sulfide components vaporized. Contributing to the incident was the absence of company procedures detailing instructions for safely draining liquids from vessels located inside buildings. Contributing to the severity of the incident was the lack of engineered safeguards (such as installed detectors, alarms, and ventilation) to control or alert of a hazardous atmosphere and an unsuccessful system for ensuring employees wear personal gas monitors.

Source:CSB.gov

August 25, 2025

H2S RELEASE DUE TO SULFIDATION CORROSION

On April 8, 2023, at about 7:45 a.m., hydrogen sulfide and sulfur dioxide were released from the sulfur recovery unit at the a Refinery in Minnesota . This event resulted in $2.235 million in property damage.

The accidental release resulted from a ruptured tube within the waste heat boiler of the sulfur recovery reaction furnace. The tube rupture was caused by a damage mechanism known as sulfidation corrosion (also known as high-temperature sulfidic corrosion). Under certain temperature conditions, sulfidation corrosion causes thinning in iron-containing materials over time due to a reaction between sulfur compounds and iron.

The company investigation also found fouling (hydrocarbon solids), which had formed on the outside of some tube wall surfaces, resulted in higher tube wall temperatures and areas of increased metal loss from sulfidation corrosion. The investigation also found that the hydrocarbons were in the boiler feed water. This indicates that the boiler feed water was not being effectively monitored, which allowed the hydrocarbon contamination to remain undetected.

The company reported that approximately 68 pounds of hydrogen sulfide and 999 pounds of sulfur dioxide were released.The company now monitors and controls boiler feedwater quality with in-line analyzers. The analyzers continuously sample boiler feedwater and strip any hydrocarbons from the sample. A carrier air then sweeps the hydrocarbons to a metal-oxide sensor for quantitative analysis. The in-line sample results provide the opportunity to evaluate hydrocarbon presence in near real-time. This allows for identification when boiler feedwater does not achieve American Society of Mechanical Engineers (“ASME”) recommendations based on hydrocarbon measurement and implementation of prompt corrective measures as necessary.
Probable Cause
Based on the company investigation, the CSB determined that the probable cause of the accidental hydrogen sulfide and sulfur dioxide release was a tube rupture in the waste heat boiler. The tube had thinned over time from sulfidation corrosion. Contributing to this event was hydrocarbon contamination in the boiler feed water that was not being effectively monitored and controlled, resulting in localized tube fouling that led to increased tube wall temperatures and thinning from the sulfidation corrosion damage mechanism.

Source:CSB.gov

August 12, 2025

YOU CANNOT IDENTIFY A PROCESS HAZARD IN HAZOP IF YOU ARE NOT AWARE ABOUT IT!

On January 31, 2023, at 6:40 a.m., an accidental release of high-pressure carbon dioxide (CO2) occurred when a vessel overpressured and catastrophically ruptured at a CO2 gas plant in Texas. Vessel fragments propelled up to 1,200 feet away and heavily damaged a control room (Figure 1). Kinder Morgan estimated the property damage to be over $14 million.

The incident occurred in the site’s CO2 compression system. Upstream of each compressor was a vessel called a scrubber that removed liquid from the CO2 feed stream. Removing liquid from compressor feed streams is critical to preventing compressor damage.
On one of the high-pressure compressor system scrubbers, a liquid level control valve (called a “dump valve”) became stuck in the open position, which was common at the site during cold weather. The outside temperature at the time was 22 degrees Fahrenheit (°F). The liquid drained out of the high-pressure scrubber through the stuck-open valve, and then high-pressure CO2 gas also started flowing out through the stuck-open valve. The high-pressure gas was released into the low-pressure drain system, and as it did, the CO2 became cold—as low as negative 30 °F (due to the Joule-Thompson effect).

The cold CO2 caused ice or hydrate to form in a drain system vessel’s outlet piping, including the piping to its emergency pressure relief valve. When this happened, the high-pressure CO2 could not vent through the pressure relief valve. The pressure in the drain system vessel continued to build until it reached about 550–700 pounds per square inch gauge (psig) and catastrophically ruptured. The vessel fractured in a brittle mode, producing fragments that flew up to 1,200 feet away.
The ruptured drain system vessel, which was made of carbon steel and measured 15 feet long by 6 feet wide, was rated to a maximum pressure of 125 psig at 650 °F. The blocked pressure relief valve had a set pressure of 15 psig. The scrubbers that drained liquid to the drain system operated at pressures ranging from 450-1,000 psig.
The failed vessel did not have instrumentation installed to allow operators to monitor conditions such as pressure, temperature, or level, and the scrubber liquid level and dump valve position were not recorded. The system’s lack of instrumentation prevented operations personnel from identifying the abnormal operating condition and taking corrective action.
In two previous process hazard analysis (PHA) reviews, the company had identified the potential for CO2 gas to blow through a scrubber dump valve, but this scenario was identified as an operational problem, not a safety problem. The PHAs did not identify the potential for ice or hydrate formation in the drain system due to a stuck-open dump valve. The PHAs also did not include a full review of the downstream closed drain system, as the closed drain system was viewed as a low-pressure utility system with low safety risk.
The company's investigation concluded that the incident resulted from the thermodynamic properties and system pressures not being sufficiently accounted for, resulting in inadequate vessel and piping design, inadequate overpressure protection, and inadequate instrumentation. The investigation recommended, among other corrective action items, that the site create an engineering design standard that addresses hazards associated with introducing high-pressure fluids into drain systems.
The company reported that 5.6 million pounds of carbon dioxide were released. In addition, the company reported that natural gas (111,000 pounds), hydrogen sulfide (2,000 pounds), carbon monoxide (1,400 pounds), sulfur dioxide (1,200 pounds), and nitrogen oxides (NOx) (260 pounds) were also released.
Probable Cause
Based on the company investigation, the CSB determined that the probable cause of the incident was the overpressure of a drain system vessel after a scrubber dump valve became stuck in the open position. Ice or hydrate formed in the vessel outlet piping, blocking the relief path. Inadequate vessel and drain system design and the lack of needed equipment instrumentation contributed to the incident.

Source:CSB.gov

July 9, 2025

DESIGN YOUR SAFETY DEVICES DISCHARGE CORRECTLY!

 On January 15, 2022, at 4:51 a.m., 201 pounds of hot methylene diphenyl diisocyanate (MDI) were accidentally released, seriously injuring two workers at a facility in Louisiana.
The company's investigation of this event concluded that the accidental release occurred when a rupture disc activated prematurely. The design activation pressure was 30 pounds per square inch (psi), and process data indicated that this emergency pressure-relief system activated at about 13 psi.

The equipment protected by this rupture disc was typically operated under vacuum conditions. At the time of the incident, however, the equipment was operating at an elevated pressure due to a problem that had developed within the system used to create and maintain the low-pressure (vacuum) conditions. Although the operating pressure was elevated, it was within safe operating limits.
When the rupture disc activated, a 400-degree Fahrenheit mixture of liquid and vapor MDI discharged into 8-inch piping that was vertically orientated downward and ended about eight inches above the concrete floor. At the time of the incident, non-essential workers were not restricted from the area near the rupture disc discharge piping because the system was operating within the safe operating limits.                               
When the high-velocity, two-phase mixture exited the discharge piping, it hit the solid floor, spraying two contract maintenance workers installing a pump near the rupture disc’s discharge piping. The two maintenance workers were hospitalized with thermal burns from exposure to the hot fluid.                                                                                                                                                                  Although Rubicon’s process hazard analysis had identified personnel exposure to hot MDI as a potential consequence of activating the rupture disc, the company had not mitigated the potential hazard of personnel working near the rupture disc discharge piping.

Source:CSB.gov

July 1, 2025

BEWARE OF MOVING EQUIPMENT IN PLANTS......

On June 14, 2021, at approximately 6:50 a.m., an accidental release of mineral oil occurred at a facility  that led to the permanent closure of the facility
Leading up to the incident, a contractor was hired to replace insulation on its heating oil piping system. To reach a portion of this piping, the contractor used a scissor lift.
As the contractor began raising the scissor lift near the work location, the top guardrail of the lift impacted a section of a ½-inch piping assembly that included a valve. This threaded piping was connected to a four-inch pipe containing mineral oil, which was part of a hot oil system that provided heating for other process equipment.
After the guardrail impacted the piping, a leak formed at the ½-inch threaded connection to the four-inch piping. The hot mineral oil, which was over 500 degrees Fahrenheit, was released as an aerosol. The mineral oil formed a white cloud and created the electrostatic conditions that most likely ignited the mineral oil.

Upon seeing the white cloud, workers responded to the release. The workers tried to contain the spill by placing absorbent barriers around mineral oil on the floor. Additionally, the workers shut off the oil heating system. The workers also lowered the pressure of the hot oil system, but the leak could not be remotely isolated from a safe location. As a result, the mineral oil ignited, and the fire grew and destroyed the facility.
The CSB estimated that less than 100 pounds of mineral oil was released between the start of the release and the time of ignition.
Probable Cause
Based on the company's investigation, the CSB determined that the probable cause of the mineral oil release was piping damage that resulted from force applied by the scissor lift. The flammable mineral oil was most likely ignited by static electricity. The hot oil system did not allow for the remote isolation of the damaged piping. Had they been able to stop the flow of mineral oil through remote isolation from a safe location, the incident could have been less severe.

Source:CSB.gov

May 24, 2025

LUBE OIL TANK FLAMMABLE ATMOSPHERE PROBABLY IGNITED BY STATIC DISCHARGE

 

Description of Incident

During start-up of the ancillary lube oil system, an overpressure event occurred, causing lube oil tank deformation and a minor loss of lube oil to the deck. There was no activation of the fixed fire & gas systems and no further escalation potential. Following a detailed investigation, it was determined that the most likely cause of the overpressure was a combustion event in the lube oil tank.

 SOURCE: https://www.stepchangeinsafety.net/alerts-moments/high-value-learning-lube-oil-tank-damage-due-to-overpressure/

The compression train has wet seals with ancillary seal and lube oil systems. Lube oil is circulated throughout the compression train and stored in an atmospheric lube oil reservoir tank. The storage tank is located on the deck below the compressors, with a pressure rating of 0.04 bar. The seal and lube oil systems are connected via a common atmospheric vent line. At the time of the incident, the seal oil system was not running.

Air was present in the lube oil tank as it would have been drawn in through the atmospheric vent when the lube oil pumps were started. A flammable atmosphere was created through low levels of hydrocarbon gas migrating into the lube oil tank and/or the formation of flammable mist of lube oil. The most likely ignition source was found to be static discharge from the lube oil.

There have been other static related incidents in industry, most commonly in the marine sector. Static charges can build up in some mineral oils due to turbulent fluid flow. Various studies have shown that, even with earthing / bonding of equipment, static discharge can still occur.

Good Practice Guidance

  • Consider looking at your operations to see if you have risk of static accumulation in your seal / lube oil.
  • Consider using anti-static additives which can help prevent static discharge.
  • Consider looking at your system to see if you can reduce the risk of static accumulation through equipment like anti-static filters.
  • Consider holistic risk assessments during plant reinstatement, including all pressure sources and interconnections between systems.
  • Consider inerting lube oil / seal oil tanks prior to start up.

December 31, 2024

Flammable atmosphere + static charge = explosion

At about 2:00 a.m. on October 15, 1990, Employee #1 was transferring an approximately 20 percent monoethanolamine (ethanolamine) solution from a process vessel, the amine regenerator, to the top of an 11,000 gallon aluminum storage tank. The ethanolamine solution had apparently entrained hydrogen gas, some of which released to the atmosphere of the storage tank upon transfer and apparently caused the hydrogen gas concentration in the tank to exceed 4 percent. A source of ignition, possibly the static charge of the falling ethanolamine solution, caused the hydrogen to explode. Employee #1 was engulfed in the release of ethanolamine solution from the ruptured tank and sustained chemical burns to his left eye. The storage tank was damaged beyond repair, and piping, valves, and windows in the immediate area were destroyed. Damage was estimated at $70,000.

Source:OSHA.gov

July 21, 2024

FIRE AND EXPLOSION HAZARDS WITH THERMAL FLUID SYSTEMS

"Incidents relating to thermal fluid systems are unfortunately more common than we might realise,
and can be extremely serious. The fire and explosion hazards with thermal fluid systems have been
re-emphasised by recent incidents. These incidents have a direct bearing on the estimated 4,000 UK
companies that operate thermal fluid systems.
Water or steam can be used as heat transfer fluids, but when high temperatures are needed
organic fluids, which are capable of forming explosive atmospheres, are often used. Although
fire and explosion hazards of low flash point flammable liquids are generally recognised, similar
hazards with high flash point materials, such as thermal fluids, are often missed. These heat transfer
fluids are often handled at temperatures above their flash point.
However, many people are unaware that heat transfer fluids based on mineral oils
degrade over time. This degradation can cause the fluid’s flash point to decrease dramatically, so
that thermal fluids which were not flammable at the operating temperature when they were initially
installed may, over time, become flammable at the operating conditions. Also, high flash point
materials (such as thermal fluids), can form explosive mist atmospheres when handled under
pressure, even at temperatures below the flash point".

Read the article in this link.


June 15, 2024

Hazards of pyrophoric materials

 Pyrophoric materials create fire and explosion hazard

There have been several explosions involving pyrophoric materials in storage tanks. It's important to take preventive measures when emptying tanks or vessels, or when opening equipment and piping for inspections and maintenance.

This bulletin explains how pyrophoric materials can form in tanks. It also describes how to prevent the explosions that can occur when pyrophoric iron sulfide is exposed to oxygen. Download and read the bulletin in this link

May 25, 2024

Storage of flammable and toxic chemicals - think about this

Continuing my previous post regarding effects of explosions, when you have large storages of flammable /toxic chemicals and are expanding your storage capacity, take into account if some thing can happen in your neighboring plant that can have fragments hitting your tanks. Here is an incident from osha.gov:

On May 27, 1994, Employees #1 through #3 were working at the XXX Chemical Plant in Belpre, OH. A catastrophic failure of a 15,000 gallon polymer reactor vessel was initiated by a runaway chemical reaction involving an abnormally high amount of 1,3-butadiene during the production of a polymer. The reactor failure and ensuing fire resulted in the complete destruction of the polymerization unit. Missile fragments from the failed reactor vessel damaged adjacent units in the plant. One fragment punctured a styrene storage tank approximately 600 ft away. This subsequently resulted in the burning of five styrene storage tanks containing approximately 3.5 million gallons of flammable products. Employees #1 through #3 were killed in the explosion