Pages

November 23, 2026

Never ignore or overlook the deviation

Many examples show that poor communication among actors, ambiguous instructions, the assignment of multiple tasks, a lack of controls or inability to treat deviations expeditiously can all lead to omitting a deviation either voluntarily or involuntarily. Around 10:30 pm at a Seveso-rated chemical plant, a sensor detected a rapid rise in conductivity inside a heat exchanger. Upon tripping the sensor alarm (at a 50 µS level), the automated safety controller isolated the circuit. A 2nd conductivitymeter, which had been idled and scheduled for replacement by the maintenance unit, showed a value of 0 µS. Not informed that this device was inoperable, technicians proceeded with sampling to remove any doubt and notified the duty manager, who analysed the situation, did not wait for the laboratory results, bypassed the conductivity-meter whose alarm had triggered, and restarted manufacturing. Ultimately, only a limited discharge of phosgene into the environment was observed, thanks to an effective 2nd safety barrier.


Source:Aria database

No comments:

Post a Comment