April 1, 2026

Confined spaces can be buildings too....argon leak asphyxiates two

On January 30, 2023, at approximately 5:30 p.m., argon gas was released at the Propulsion Systems facility in Utah. Exposure to the argon gas fatally injured two employees, who asphyxiated.
The company treated carbon fiber blocks at the facility. As part of the treatment, a specialized vessel (autoclave) containing carbon fiber blocks was pressurized with argon gas. On the day of the incident, two employees were working to locate argon leaks and troubleshoot the vessel’s pressure control system. During this work, the autoclave did not contain carbon fiber blocks. Throughout the workday, the vessel was pressurized with argon gas several times, but the task was not completed by the end of the employees’ shift. The employees changed out of their work clothes and removed their personal oxygen monitors. However, before meeting with the oncoming shift workers, the two employees returned to the basement. The crew arriving for the next shift found their two coworkers unconscious in the basement’s stairway. Emergency responders transported the two employees to the hospital, where they were declared deceased.
The company’s investigation found that argon had leaked through the seals of the pressurized vessel while the basement’s ventilation system was off, which allowed the basement (about 4,500 cubic feet) to begin to fill with argon and create an oxygen-deficient atmosphere. The company’s investigation did not determine why the two employees returned to the basement at the end of their shift, however. After the incident, the company classified the basement as a confined space and installed an oxygen monitoring system. The company also implemented safeguards to prevent entry into the basement when the oxygen concentration is unsafe, the exhaust ventilation fan is off, or the vessel is pressurized.
Probable Cause
Based on the company's investigation, the CSB determined that the probable cause of the incident was the release of argon gas from the autoclave into a confined area. The two workers were fatally injured when they entered this oxygen-deficient environment. The lack of effective engineering controls, such as forced air ventilation and continual oxygen monitoring, contributed to the severity of the incident.

 Source;CSB.gov 

March 23, 2026

On the day of the incident, a contract worker used steam to heat the contents of a railcar to facilitate its unloading into process equipment. After the railcar was unloaded, the worker needed to remove the steam and condensate hoses from the railcar . The contractor verified that the steam and condensate isolation valves were closed and that steam was no longer draining from the condensate drain valve. While removing the steam hose from under the railcar, the contractor was sprayed with steam and hot condensate. The contractor was transported and admitted to a hospital for treatment.

 

The company's investigation identified that the typical practice used at the facility to isolate and depressurize the steam hose was to close Valve A while having Valve B and Drain Valve 1 open to allow residual steam to flow out of the hose. However, Valve A was broken in the open position and could not be closed. Instead, the contract worker closed Valve B, left Drain Valve 1 closed, and opened Drain Valve 2 (visually obstructed in by the steam supply hose) to drain both the condensate hose and the steam hose. Because of how the heating coil was configured within the railcar, this configuration trapped condensate in the steam hose.
The company's investigation found that when workers first identified the broken valve (Valve A), they should have used stop work authority to prevent the unloading equipment from being used until the valve was repaired. The company’s investigation also concluded that its written operating procedure did not effectively describe the process of draining steam or hot condensate from the railcar. In addition, the procedure did not explain how to verify that there was no pressure on the steam or hot condensate hoses. No instruments (such as a pressure gauge) or other safeguards were available to warn workers that the steam hose contained a dangerous amount of condensate.
Probable Cause
Based on the company's investigation file, the CSB determined that the probable cause of the incident was disconnecting a hose from a railcar that contained steam and hot condensate. A broken isolation valve on the steam supply piping changed how the steam and condensate hoses were isolated and drained, contributing to the incident. The lack of instrumentation or other safeguards to warn employees that the loading hose held a dangerous amount of condensate contributed to the incident.

 Source:CSB.gov 

March 18, 2026

IMPROPER LOTO OF ISOLATION VALVE OF PUMP CAUSES AN INCIDENT

On December 20, 2021, at approximately 9:30 a.m., a release of molten polymer caught fire, seriously injuring an employee in a company in Virginia. In December 2021, the company planned to perform maintenance work on a rupture disc used to protect one of its molten polymer positive displacement pumps from potential high-pressure conditions. On December 18, an operator prepared the equipment for maintenance. The preparation involved turning the pump off, locking and tagging its electrical switch, and closing, tagging, and locking the pump’s inlet and outlet isolation valves. The keys for the three locks were put into a lock box.
On December 20, 2021, the day of the incident, a different company operator issued safe and hot work permits to two maintenance workers to perform the rupture disc maintenance. Each of the two maintenance workers applied their personal lock to the lock box. The work involved using a propane torch to heat the external surface of the equipment and melt the polymer inside so that the rupture disc could be removed. One of the maintenance employees removed the bolts from the rupture disc holder, while the second worker acted as a “standby” and observed the work. Both workers wore the standard personal protective equipment (PPE) used at the plant, plus a face shield and an aluminized jacket. When the maintenance worker used the propane torch before removing the last bolt, the rupture disc and the bolt were forcefully ejected, spraying the employee with hot (500 degrees Fahrenheit) molten polymer. The propane torch ignited the molten polymer, starting a fire.
The standby worker pulled the emergency alarm and used the plant radio system to call for help. Emergency responders extinguished the fire and transported the injured maintenance worker to a nearby hospital with a burn center. The worker was admitted for treatment of his injuries, which included third-degree burns. The most severe injuries were to the workers’ legs. The worker’s denim jeans did not offer the same level of protection as his aluminized jacket.The company reported that approximately 50 pounds of molten polymer were released. The polymer primarily consisted of nylon 6 and some caprolactam.
The company's investigation found that the pump’s outlet valve had been incorrectly locked in the open position when it should have been closed (Figure below). On the day of the incident, the employees saw that the inlet and outlet valves had been tagged and locked. However, they did not verify that the valves were closed.

 

 Simplified equipment drawing, highlighting the open outlet valve (left image)

In response to the incident, the company upgraded the PPE requirements to include aluminized clothing for line opening work on its molten polymer equipment.

Probable Cause
Based on the company's investigation, the CSB determined that the probable cause of the incident was not effectively isolating and draining the piping before having workers disassemble the rupture disc. As a result, after most of the rupture disc’s flange bolts were removed, the pressurized piping caused molten polymer to spray out of the rupture disc’s holder. The molten polymer ignited, leading to a fire that seriously injured one employee. Not verifying that the equipment was effectively isolated contributed to the incident. If any employee or supervisor had verified that the locked valves were closed, the incident could have been prevented. Not wearing aluminized pants with the aluminized jacket contributed to the severity of the incident.

Source:CSB.gov 

March 13, 2026

IMPROPER CLEARING CAUSES A SERIOUS INJURY

 On March 22, 2021, at approximately 12:30 p.m., an explosion and fire occurred at a  Refinery in California. The explosion and fire seriously injured one contract worker.Leading up to the incident, the  refinery was shut down for turnaround maintenance. The planned maintenance work included removing a section of carbon steel piping in the Fluidized Catalytic Cracking (FCC) unit that typically contained gasoline. Two days before the incident, on March 20, 2021, 50 gallons of chemical cleaning water containing hydrocarbons were released when workers opened a flange to install a blind (metal plate) to isolate a section of 18-inch piping.
On March 22, 2021, the day of the incident, the 18-inch piping was isolated with the blind at one end and the other end transitioning to a section of 10-inch piping open to the atmosphere with drain piping between the blind and the open 10-inch end. To remove the piping, Phillips 66 tasked a crew of contract workers to cut the 18-inch piping at the location shown in Figure.


Before the cutting began, an operator performed flammable gas testing at the work area, showing no flammable gas was present. Operators also walked the job with the contractor’s supervisor. After this, the operators issued a work permit authorizing the contractors to use an electric angle grinder with a cutting wheel to cut the piping. The permit stated that the piping was isolated, vented, depressured, and chemically cleaned. Because the work area was elevated about 10 feet above ground, fire blankets were installed, creating an enclosure to contain sparks created during the pipe-cutting work.

As the lower portion (from the four to six o’clock position) of the piping was being cut, liquid flowed out, and the worker stopped cutting. The drain piping was unplugged using a wire, allowing the fluid to drain. The contractors contacted operations personnel to evaluate the piping. The operators rechecked the piping and confirmed that no flammable gas was present. One of the contract workers invoked his stop-work authority and refused to continue cutting on this piping because the liquid smelled like gasoline. One of the operators described the odor as pine and attributed it to the substance used during chemical cleaning. Ultimately, two operators and a contractor supervisor agreed that the liquid was primarily water. At approximately 12:30 p.m., two hours after the work was stopped, another contract worker was sent to finish cutting the pipe. When the worker started the angle grinder, an explosion and fire occurred. The contractor suffered serious burn injuries from the combustion event and was transported and admitted to a hospital for treatment.
The company's investigation determined that the piping contained flammable hydrocarbons because the plugged drain prevented the piping from being flushed and cleared as intended. The flammable gas testing performed at the work area did not identify the flammable vapor inside the piping. In addition, the company’s investigation concluded that when the contract worker used his stop-work authority and refused to cut the piping, his safety concerns should have been elevated to operations and maintenance supervisors for help ensuring the job was safe before resuming work – but they were not. The company estimated that less than half a gallon of gasoline was released.
Probable Cause
Based on the company's investigation, the CSB determined that the probable cause of the incident was that the piping segment was not effectively flushed and drained before the contract workers were authorized to cut the piping. Not recognizing the presence of flammable gas contributed to the incident.

Source: CSB.gov

February 13, 2026

2 KILLED DUE TO IMPROPER CLEARANCE

In a crude oil distillation unit, tests showed that the flare system valve was not providing effective isolation and would require eventual removal for overhaul at a scheduled shutdown of the flare. A ‘cold work’ permit to work was issued two days prior to the incident. Alternate flange bolts were removed and the other bolts lubricated as a standard practice to save time. Sufficient bolts remained at all times to retain the flange seals. There was at that time no need to verify line conditions. Two contractors wearing breathing apparatus completed the work. When almost all the bolts were undone, liquid leaked from the gap between the flanges and gas escaped from the top of the joint.
The men stopped work, came down to ground level and sought advice. The supervisor checked the
platform and saw gas issuing from the top and liquid leaking from the bottom of the flange. He concluded that neither was under pressure and that the quantity of liquid was small. Without any further tests assured the contractors that it was safe for work to continue. The fitters remained concerned, thus asked and received 'spark proof' tools. Liquid continued to leak as more bolts were removed then, as the last bolt was undone and the crane took the strain and started to lift the valve, the spacer suddenly sprang upwards. A large quantity of liquid was released, a flammable vapour cloud formed and ignited by the nearby compressor. Two workers died in the incident.
Key learning points
A tower scaffold with a working platform and access ladder had been erected for work on the valve but due to access restrictions, it was necessary to climb over or under it. This seriously limited the route of escape. Work on the valve should not started prior to verification of the isolation and should not have continued after the first leak occurred until all doubt about the safety of the situation had been resolved. The absence of the spark arrester on the compressor was not known of until after the incident.

Source:IChemE 

 

February 5, 2026

EXPLOSION IN SPENT ACID TANK DURING HOT WORK

A massive explosion destroyed a large storage tank containing a mixture of sulphuric acid and flammable hydrocarbons at an oil refinery. One contract worker was killed, eight others were injured, and sulphuric acid from collapsed and damage tanks polluted the local river. The explosion occurred during welding operations to repair a catwalk above the sulphuric acid tank, when flammable hydrocarbon vapour was ignited by welding sparks. This resulted in a powerful explosion inside the tank.
Key learning points
On the day of the accident, flammable gas testing was performed only at the start of the hot work, but monitoring was not conducted for the duration of the repair activities. It is also important as to where the explosive atmosphere measurements were made. Through the five hours between the last gas test and the explosion, the ambient temperature raised significantly. This warming caused the hydrocarbons inside the tank to vapourise. The resulting flammable vapour leaked out from corrosion holes in the tank into the work area. The company had a hot work program that included written permits, but the program was inadequate. Hot work was allowed near tanks that contained flammable materials without continuous atmospheric monitoring and the control of welding sparks was not required.

Source:IChemE 

 

February 1, 2026

EXPLOSION IN TANK DURING MAINTENANCE

An explosion occurred in a wholesale and retail storage facility in 2001. Two contract workers were carrying out maintenance operations inside a 5,090 m³ atmospheric storage tank. The closed floating roof tank usually contained premium grade gasoline but it was emptied for the maintenance job. The event occurred during cleaning operations. The activity, performed by employees of an external company, consisted in removing residue from the tank bottom by means of scraping. The most plausible theory is that spark was created by one of the worker's tools (boot soles points, metallic scraper, steel snap hook, etc.). Within an explosive atmosphere, this could have caused an explosion. The two workers were seriously injured in the incident. The tank was not repairable and the operation of the storage facility was interrupted for approximately two months.
Key learning points
The distance of the floating roof from the tank bottom at the time of the accident was approximately 1.2 m. The working space in this situation was limited. The empty tank that exploded normally contained premium grade gasoline. The gasoline vapours which were still in the tank caused the explosion. The tank was equipped with only one manhole. Apparently, when the incident occurred not all the vents were open; it is likely that the atmosphere was not homogenous and that explosive pockets of vapour/air also existed. The ventilation system set up to evacuate gasoline vapours was shut down for the cleaning operations to take place. What is also not always recognised is that gasoline collects in welds, pontoons (of floating rooves), particularly if they are not well maintained, small pits and crevices on the surface of the steel, within the residues on the tank floor. This means that there is a continual production of vapours
even after the tank has been emptied. This means that explosive atmosphere measurements need to be regularly repeated as well as constant ventilation. Finally, the limited space of movement of the workers was also an adverse factor in their escape.

Source:IchemE