A five-person crew was valving in a second stage reheater at an electric
power generation station. They were slowly opening two valves to bring
the reheater online. Two of the employees were stationed at one valve,
and the other three were at the second valve. Two other employees were
working in the immediate area, observing the reheater's drain tank
levels after having adjusted an automatic valve about 30 minutes before.
The drain line for the reheater ruptured downstream of the valves,
releasing steam and hot water into the area. The rupture was caused by
excessive pressure in the line as a result of a water hammer. The water
hammer was caused by the presence of lower pressure on the downstream
side of the valves than on the upstream side. This produced a back flow
in the line. The operating procedure for the valves in the line during
start up operations had been changed earlier in the year to eliminate
water hammer that had occurred previously. However, the new changes were
not incorporated into the written operating procedures being used at
the time of the accident. Seven employees (all five members of the work
crew plus the two other employees working in the area) received
second-degree burns to multiple parts of their bodies. They were
hospitalized for their injuries.
RISK BASED PSM PROCESS SAFETY MANAGEMENT INDIA CONSULTANT INCIDENT INVESTIGATION HAZOP TRAINING ROOT CAUSE ANALYSIS AND LESSONS FROM INCIDENTS
November 30, 2019
November 27, 2019
Steam flushing incident
At approximately 9:30 a.m. on January 19, 2005, Employee #1 and Employee
#2, were isolating and cleaning a
series of three pumps at a refinery in California,
while Employee #3 observed the cleaning operation from a distance. The
three workers were starting up the refinery's crude unit. They were
experiencing screen plugging from crude unit particles inside the crude
unit's prefractionator reboiler pump (pump). The screens commonly become
plugged during start-up operations. After the charge pump is isolated,
workers clean the pump body by injecting pressurized steam into it.
Normally the mix of residual crude oil and pressurized steam is removed
through a small outlet in the valve body. Employee #1 connected a 40 psi
steam line to the top of the pump body. The flexible removable steam
line connects to a Chicago fitting on the top of the pump. Just before
the explosion, Employee #1 had cracked open the steam line, letting
steam into the pump. An uncontrolled pressure event immediately ensued.
The overpressurization of the pump body assembly caused the pump suction
flange, strainer outlet flange, and flex connector to blow out
violently. The spraying hot oil and the fire started by the explosion
caused burns to Employees #1, #2, and #3. Employee #1 sustained third
and second degree burns over 50 percent of his body and later died.
Employee #2 suffered first and second degree burns over his back.
Employee #3 suffered first degree burns on his face. Employees #1 and #2
were treated at the Hospital.
Employee #3 was treated locally.
Source: OSHA.gov
Source: OSHA.gov
November 24, 2019
OSHA's Top 10 Most Frequently Cited Standards FY 2018
OSHA's Top 10 Most Frequently Cited Standards
(Source: https://www.osha.gov/Top_Ten_Standards.html
for Fiscal Year 2018 (Oct. 1, 2017, to Sept. 30, 2018).
The following is a list of the top 10 most frequently cited standards following inspections of worksites by federal OSHA. OSHA publishes this list to alert employers about these commonly cited standards so they can take steps to find and fix recognized hazards addressed in these and other standards before OSHA shows up. Far too many preventable injuries and illnesses occur in the workplace.
for Fiscal Year 2018 (Oct. 1, 2017, to Sept. 30, 2018).
The following is a list of the top 10 most frequently cited standards following inspections of worksites by federal OSHA. OSHA publishes this list to alert employers about these commonly cited standards so they can take steps to find and fix recognized hazards addressed in these and other standards before OSHA shows up. Far too many preventable injuries and illnesses occur in the workplace.
- Fall protection, construction (29 CFR 1926.501) [related OSHA Safety and Health Topics page]
- Hazard communication standard, general industry (29 CFR 1910.1200) [related OSHA Safety and Health Topics page]
- Scaffolding, general requirements, construction (29 CFR 1926.451) [related OSHA Safety and Health Topics page]
- Respiratory protection, general industry (29 CFR 1910.134) [related OSHA Safety and Health Topics page]
- Control of hazardous energy (lockout/tagout), general industry (29 CFR 1910.147) [related OSHA Safety and Health Topics page]
- Ladders, construction (29 CFR 1926.1053) [related OSHA Safety and Health Topics page]
- Powered industrial trucks, general industry (29 CFR 1910.178) [related OSHA Safety and Health Topics page]
- Fall Protection–Training Requirements (29 CFR 1926.503) [related OSHA Safety and Health Topics page]
- Machinery and Machine Guarding, general requirements (29 CFR 1910.212) [related OSHA Safety and Health Topics page]
- Eye and Face Protection (29 CFR 1926.102) [related OSHA Safety and Health Topics page]
November 20, 2019
November 16, 2019
Explosion due to suspended graphite cloud and static electricity
On September 3 2018, a blast destroyed one of 400 buildings at the RDM plant in South Afirca, which manufactures artillery ammunition.Eight workers were killed.
As per a report published Herald Live, "Based on extensive testing, assessments and elimination of other initially suspected causes, the most likely cause of the explosion was a build-up of electrostatic electricity in a suspended graphite cloud due to the triboelectric effect, and a subsequent discharge which ignited airborne propellant in the blending drum.”
Read the article in this link
As per a report published Herald Live, "Based on extensive testing, assessments and elimination of other initially suspected causes, the most likely cause of the explosion was a build-up of electrostatic electricity in a suspended graphite cloud due to the triboelectric effect, and a subsequent discharge which ignited airborne propellant in the blending drum.”
Read the article in this link
November 12, 2019
Control of Hazardous Energy by Lock-out and Tag-out
Control of Hazardous Energy by Lock-out and Tag-out: Why Lock-Out and Tag-Out?Lock-out and tag-out (LOTO) is a critical part of a strong all-around safety program. In LOTO, maintenance employees work with production employees to positively prevent all forms of hazardous energy from causing harm. Hazardous e
November 8, 2019
November 4, 2019
Loss of containment incident
On September 21, 2003, Employee #1 and several coworkers were working at
a chemical plant that deals with nitric oxide. On the day of the
accident, a major leak occurred in a stainless steel distillation
column. The nitric oxide leaked into the facilities surrounding vacuum
jacket and into the atmosphere through a pump, which controls a high
quality vacuum inside the jacket to minimize transmission of heat toward
the cryogenic distillation columns. A brown cloud quickly formed and
the temperature and the pressure inside the distillation column and its
surrounding vacuum jacket began to rise. The leak was detected and the
vacuum pump was turned off to halt the leakage of nitric oxide into the
atmosphere, allowing the pressure inside the column and vacuum jacket to
stabilize around 130 psi. Although stabilized, the pressure was far
above the normal pressure of less than or equal to atmospheric pressure
(14.7 psi). Approximately 3 hours later, an explosion occurred. The
operation and process were destroyed, and debris flew through the plant.
Employee #1 suffered lacerations due to flying glass and was treated at
a local hospital, where he received stitches and then released. A
detailed investigation determined that the cause of the explosion was
most likely due to something inside the vacuum jacket initiated the
dissociation of nitric oxide, a reaction that is very rapid, exothermic,
and self-propagating once started.
Source Osha.gov
Source Osha.gov