Pages

May 30, 2024

Do you have emergency procedures for polymerisation reactions?

On January 31, 2006, a runaway reaction occurred at XXXX, while employees were making a  product. The polymerization reaction included toluene, cyclohexane, n-butyl acrylate, and benzoyl peroxide. According to the employer's records, there were 2,689 pounds of the solvent blend and 1,923 pounds of N-Butyl Acrylate in a Pfaudler reactor (M-1). Two 55-gallon drums and one 330-gallon IBC tote were positioned in front of reactor M-1. The containers held a solvent blend of toluene, cyclohexane, and benzoyl peroxide. At the time of the incident, the contents of one of the drums and a portion of a second drum had been transferred to the M-1 reactor. Employee #1 walked away from the reactor,
intending to turn a valve on the M-5 reactor to begin a nitrogen purge and move the contents of M-5 to M-1. While walking down a stair to perform this task, Employee #1 heard a loud, high-pitched sound. He immediately went back up and observed the Teflon 18 in. envelope gasket from M-1 hanging down from the manway and vapors coming through the opening. Other employees began to hear the sound. After Employee #1 observed the vapors being emitted, he walked outside and met other employees outside the production door, on the Northwest side of the building. Employee #2 was operating a forklift inside the drumming area when he heard the sound. He left the area and met with Employee #3 and Employee #4. They walked up to the Northwest side of the building. Employee #5 instructed Employee #3 to go get the Plant Manager. Employee #5 then donned a full-face respirator and entered the building to turn on the chill water to the reactor.
After a few seconds, Employee #5 returned after failing to obtain a good seal on the respirator and smelling vapors. Employee #1 then donned the respirator and went inside the building. Employee #3 and Employee #6 walked up and joined the other employees outside the production door. When Employee #1 exited the building, an explosion occurred. Twelve employees and two bystanders sustained various injuries. Five of the employees were hospitalized with various injuries, and one died later of burns.

Source: OSHA.gov

May 25, 2024

Storage of flammable and toxic chemicals - think about this

Continuing my previous post regarding effects of explosions, when you have large storages of flammable /toxic chemicals and are expanding your storage capacity, take into account if some thing can happen in your neighboring plant that can have fragments hitting your tanks. Here is an incident from osha.gov:

On May 27, 1994, Employees #1 through #3 were working at the XXX Chemical Plant in Belpre, OH. A catastrophic failure of a 15,000 gallon polymer reactor vessel was initiated by a runaway chemical reaction involving an abnormally high amount of 1,3-butadiene during the production of a polymer. The reactor failure and ensuing fire resulted in the complete destruction of the polymerization unit. Missile fragments from the failed reactor vessel damaged adjacent units in the plant. One fragment punctured a styrene storage tank approximately 600 ft away. This subsequently resulted in the burning of five styrene storage tanks containing approximately 3.5 million gallons of flammable products. Employees #1 through #3 were killed in the explosion

May 21, 2024

Explosions can have effects on neighbouring plants

Due you consider the effects of explosions from nearby plants that can affect you? Shrapnel from explosions can be thrown a large distance. In one case an urea plant reactor top flange and attached head from vessel were thrown about 385 feet (117.4 meters)  after it failed due to environmental stress cracking. Read the report in this link

Another incident (courtesy of osha.gov) is given below: 

On May 1, 1991, at the IMC Fertilizer, Inc., (IMCF)/Angus Chemical Company plant located in Sterlington, LA, a fire occurred in the area of a waste gas vent compressor (RJ-291) in the nitroparaffins (NP) plant. A few moments after the fire started, a series of explosions destroyed a large section of the NP plant, sending shrapnel north and east of the plant. Large debris weighing up to 150 pounds was hurled almost a mile away. Employees #1 through #8 of IMCF were killed and 42 were injured. In addition, approximately 70 residents of the town were injured and numerous businesses and residences were severely damaged.

May 16, 2024

Be careful when you deal with automated systems

With many valves being able to be operated from control room and also automated, this raises a hazard when carrying out maintenance. These automated valves should not open suddenly when maintenance work is going on. Do you have clear procedures to correctly Lock Out Tag Out and Try out such systems?

Read this incident:

At 9:00 a.m. on May 23, 2023, Employee #1 and Employee #2, both maintenance workers for a petroleum refinery were troubleshooting an automated valve in the "Prime G Unit". Flammable gasoline/hydrocarbons in the piping and flange portion of the automated valve were released causing an explosion and fire. Employee #1 sustained 3rd degree burns to over 83% of his body and was hospitalized. Employee #2 sustained 3rd degree burns to over 93% of his body and died on May 26, 2023. 

Source OSHA.gov