A leak in a hydrocarbon refrigerant system formed a vapor cloud that was drawn into the inlet of a steam boiler. The increased fuel to the boiler caused rapidly rising pressure within a steam drum. The rapidly rising pressure exceeded the capacity of the boiler’s safety valve and the steam drum ruptured. The boiler rupture was close enough to the gas leak to ignite the vapor cloud and produce an explosion due the confined nature of the gas lea and an ensuing fireball. The fire took eight hours to extinguish. The explosions and fire destroyed a portion to the LNG plant and caused 27 deaths, and injury to 72 more.
December 28, 2021
December 24, 2021
LNG leak causes sewer explosion
LNG leak from open run-down line during a pipe modification project. LNG entered an underground
concrete storm sewer system and underwent a rapid vapor expansion that overpressured and ruptured
the sewer pipes. Storm sewer system substantially damaged.